Substation Equipment




Differential relaying is the universal bus and transformer protection scheme. The inrush current associated with power transformers requires a special differential relay utilizing filters to provide harmonic restraint to differentiate between energizing current and fault current.

Instantaneous and time delay overcurrent relays are the most common protective devices used on shunt reactors, capacitors and station service equipment.

 

CONTROL

Transmission line faults are predominantly temporary, and automatic reclosing is a necessary complement to the protective relaying function. The reclose time must be greater than the time required to dissipate the arc products associated with the fault. This varies with the system voltage and ranges from 15–20 cycles at 138 kV to 30 cycles for the 800 kV systems. Automatic reclosing requires that proper safety and operating interlocks are provided.

Rotating equipment, transformers, and cables do not, in general, have temporary faults, and automatic reclosing is not provided.

 

MONITORING

The importance of monitoring the performance of power system and equipment has steadily increased over the years.

Oscillographs and other fault recorders such as sequence of events are, by nature, automatic devices. The time frame involved in recognizing and recording system parameters during a fault precludes any operator intervention. The most common initiating values are currents and voltages associated with the fault itself. Phase currents increase, phase voltages decrease, and there is normally very little ground current, so all of these are natural candidates for trigger mechanisms. They are revealed in the oscillographic records and are an essential element in analyzing performance. Figure 6 is a typical record of a single phase to ground fault and unsuccessful highspeed reclose.

With the advent of digital relays, the situation changed dramatically. Not only could the relays record the fault current and voltage and calculate the fault location, they could also report this information to a central location for analysis. Some digital devices are used exclusively as fault recorders.

 


Дж.Зумерчик-Макмиллан. Энциклопедия энергии. Том 1.
ЭЛЕКТРОЭНЕРГЕТИКА, СИСТЕМЫ ЗАЩИТЫ КОНТРОЛЯ И МОНИТОРИНГА

Релейная защита – это отрасль электроэнергетики, связанная с принципами проектирования и эксплуатации оборудования (называемого "реле" или "реле защиты"), которое обнаруживают аварийные условия питания системы и как можно быстрее производят корректирующие действия, чтобы вернуть энергосистему в нормальное состояние. Быстрота реагирования является одним из важнейших параметров системы релейной защиты, часто требуется время срабатывания порядка нескольких миллисекунд. Следовательно, вмешательство человека в защитные операции системы не представляется возможным. Ответные меры должны быть автоматическими, быстрыми и должны вызывать минимальное количество сбоев в энергосистеме.

 